ao link
Twitter
Facebook
Linked In
Twitter
Facebook
Linked In

You are viewing 1 of your 1 free articles

Evacuation plans should be developed for all high-rise buildings, says Grenfell Inquiry judge

Building owners should be required by law to develop evacuation plans for all high-rise buildings, the judge leading the Grenfell Tower Inquiry has recommended.

Linked InTwitterFacebookeCard
Picture: Lucy Brown
Picture: Lucy Brown
Sharelines

Evacuation strategies for all new high rises, regular fire door inspections, “vigorous” progress removing cladding: read the Grenfell Inquiry recommendations here #ukhousing

Evacuation plans should be developed for all high-rise buildings, says Grenfell Inquiry judge #ukhousing

Sir Martin Moore-Bick unveiled his long-awaited phase one report today. He made a series of recommendations under 17 separate headings that will have a major impact on the housing sector if they are adopted.

They include the development of evacuation plans for all high rises – including personally developed plans for residents who would struggle to evacuate themselves and the provision of alarm systems.

The judge also recommended an “urgent” inspection of fire doors in all properties with separate dwellings – not just high rises.


READ MORE

Grenfell forum must be set up ‘urgently’ to tackle inquiry recommendations, says firefighters’ unionGrenfell forum must be set up ‘urgently’ to tackle inquiry recommendations, says firefighters’ union
Grenfell Inquiry: ACM cladding was ‘primary cause of fire spread’ and tower did not comply with regulations, judge rulesGrenfell Inquiry: ACM cladding was ‘primary cause of fire spread’ and tower did not comply with regulations, judge rules
Grenfell Inquiry: round-up of Sir Martin Moore-Bick’s phase one conclusionsGrenfell Inquiry: round-up of Sir Martin Moore-Bick’s phase one conclusions
Grenfell Tower Inquiry report: the recommendationsGrenfell Tower Inquiry report: the recommendations
Recommendation rejected by Pickles as ‘disproportionate’ in 2013 repeated in Grenfell Tower InquiryRecommendation rejected by Pickles as ‘disproportionate’ in 2013 repeated in Grenfell Tower Inquiry

He stopped short of calling for the retrofitting of sprinklers in all tall buildings despite some of his expert witnesses “urging” him to, reasoning that he had not yet studied the evidence on this point.

In a letter to the prime minister, Sir Martin said: “The report contains a number of recommendations which I am confident will improve the safety from fire of those who live in high-rise buildings.

“They require urgent action to be taken by the government and others who have responsibility for the oversight and direction of the emergency services, in particular the London Fire Brigade. I look forward to their implementation without delay.”

The recommendations, summarised below, range from improved fire signage to the provision of building plans to emergency services.

He called for “vigorous” progress in the slow rate of the removal of dangerous cladding – with particular attention to be applied to decorative features that could allow the fire to spread horizontally.

The provision of evacuation strategies – which will include the retrofitting of manual or smart alarms to alert residents – will represent a giant shake-up of fire strategy for building owners and social landlords.

Since 1962, the sector has relied on ‘stay put’ advice to residents, which is predicated on the building withstanding the spread of fire and actively discourages the use of alarms.

Sir Martin has not advocated dropping this advice in all circumstances, but he is essentially requiring steps to be put in place to provide a ‘plan B’ if this advice fails.

He also said the issue of whether the recommendations should apply to buildings of 11m, rather than the current threshold of 18m, would be a matter considered in Phase Two.

His recommendations are summarised below.

The Grenfell Tower Inquiry recommendations: phase one

The Grenfell Tower Inquiry recommendations: phase one

Picture: Getty

Evacuation

There were no plans to evacuate Grenfell Tower available. Sir Martin Moore-Bick, chair of the Grenfell Inquiry, recommended:

  • The development of national guidelines for carrying out partial or total evacuations of high-rise buildings – including protecting fire access routes and procedures for evacuating people who require assistance
  • Fire services develop policies for partial or total evacuation of high rises
  • Owner and manager be required to draw up and keep under review evacuation plans, with copies provided to local fire and rescue services and placed in an information box on the premises
  • All high-rise buildings be equipped with facilities to enable the sending of an evacuation signal to the whole or a selected part of the building
  • Owners and managers be required by law to prepare personal evacuation plans for residents who may struggle to do so personally, with information about them stored in the premise’s information box
  • All fire services be equipped with smoke hoods to help evacuate residents down smoke-filled stairs

Fire doors

Sir Martin said it is apparent that “ineffective fire doors allowed smoke and toxic gases to spread through the building more quickly than should have been possible”, and that missing self-closers played an important role. He recommended:

  • An urgent inspection of fire doors in all buildings containing separate dwellings, whether or not they are high rises
  • A legal requirement on the owner or manager of these buildings to check doors at least every three months to ensure self-closing devices are working effectively

Sprinklers

Noting the recommendation from the coroner investigating the Lakanal House fire that the use of sprinklers be encouraged, Sir Martin said that some of his experts had “urged me to go a step further and to recommend such systems be installed in all existing high-rise buildings”.

He said that sprinklers have “a very effective part to play” in an overall scheme of fire safety, but that he had not yet heard evidence about their use. He said that he could make no recommendations at this stage, but that he would consider the matter in phase two.

Internal signage

Floor numbers in the tower were not clearly marked and markings were not updated when the floor numbers changed following the refurbishment. Sir Martin said that all high-rise buildings should have floors clearly marked in a prominent place, which would be visible in low light or smoky conditions. Given that not all residents of Grenfell could read fire information signs, he said this should now be provided in a means that all residents can understand.

Use of combustible materials

Sir Martin said the original fire in the kitchen was no more than an ordinary kitchen fire that spread to the cladding because of “the proximity of combustible materials to the kitchen windows” – such as the uPVC frames.

He said this is a matter that “it would be sensible” for owners of other high-rise buildings to check.

He said he would “add his voice” to those who have expressed concern about the slow pace of removal work for more than 400 other tall buildings in England with aluminium composite material cladding.

A total of 97 buildings in the social housing sector and 168 in the private sector have not yet seen the work complete. Sir Martin said the work must be completed “as vigorously as possible”.

He said particular attention should be paid to decorative features, given the crucial role played by the architectural crown at Grenfell in spreading the fire around the building.

Given the decision to ban combustible materials on new buildings last year, he did not call for further restrictions on their use.

Fire service: knowledge and understanding of materials in high-rise buildings

Sir Martin raised concern that junior firefighters were not aware of the danger of cladding fires, and that the London Fire Brigade (LFB) was unaware of the combustible materials used to refurbish Grenfell Tower.

He therefore recommended:

  • That the owner and manager of every high-rise building is required to provide details of external walls and the materials used to the local fire service, and inform them of any changes
  • To ensure that fire services personnel at all levels understand the risk of cladding fires

Plans

Sir Martin said that a lack of plans did not “unduly hamper” fire services at Grenfell, as each floor was laid out in the same way. However he warned that another building with a more complex layout could pose problems. He recommended:

  • That owners and managers of high-rise buildings are required by law to provide paper and electronic versions of building plans of all high rises to local fire services
  • To ensure the building contains a premises information box, including a copy of floor plans

Lifts

Firefighters were unable to use a mechanism that allows them to take control of the lifts on the night of the fire, hampering their progress and meaning residents could still use the lifts, “in some cases with fatal consequences”. Sir Martin therefore recommended:

  • That the owner and manager of every high-rise building be required by law to carry out regular inspections of any lift required for use by firefighters and the mechanism that allows them to take control of it

Section 7(2)(d) of the Fire and Rescue Services Act

The judge was concerned that inspections of the tower by the fire service before the fire were not enough to meet their responsibilities under this act. He recommended:

  • A revision of the guidance for the London Fire Brigade, and training for all officers above the rank of crew manager in inspecting high-rise buildings

Co-operation between emergency services

There was a lack of communication between each emergency service at Grenfell, with each declaring a major incident at different times without telling each other. Sir Martin recommended several changes to ensure better communication in the future.

Personal fire protection

Sir Martin decided not to issue a recommendation that individual flats be provided with fire extinguishers or fire blankets, noting concerns that this could encourage residents to fight fires rather than escape and call the emergency services.

Communication between the control room and the incident commander

While guidance calls for a “free flow” of information between a fire service control room and the commanding officer on the ground, that often does not happen. Sir Martin therefore recommended:

  • A review of policies by the LFB on this matter, including training for all officers who could serve as incident commanders and senior control room officers.
  • A dedicated communications link between the senior officer and the incident commander

Emergency calls

Even allowing for the pressure of the night, Sir Martin said that fire survival guidance calls were not handled in an “appropriate or effective way”. He therefore recommended:

  • Amending of policies and training for control room officers
  • That all fire services develop policies for multiple fire survival guidance calls
  • Electronic systems to record and display calls
  • A policy for managing a transition from ‘stay put’ to ‘get out’ and training for call handlers in delivering this change of advice

Command and control

Sir Martin said firefighters too frequently “acted on their own initiative”, resulting in a duplication of effort. He called for better policies to ensure:

  • Better control of training and deployment
  • Information is obtained from crews after they have deployed

Equipment

Sir Martin made some recommendations for improvements to fire service equipment, including radios and the command support system.

Testing and certification of materials

Sir Martin said this is an issue that will be investigated “early in phase two”, along with an assessment of “whether the current guidance on how to comply with the building regulations is sufficiently clear and reliable”.

He also said the inquiry would investigate whether a ‘prescriptive’ regime of regulation was necessary. However, as these issues have not yet been examined by the inquiry he did not make any recommendations.

Grenfell Tower Inquiry: full coverage

Grenfell Tower Inquiry: full coverage

Evacuation plans should be developed for all high-rise buildings, says Grenfell Inquiry judge

Sir Martin calls for landlords to develop evacuation policies on all high-rise buildings as well as recommending an “urgent” inspection of fire doors in all properties.

Click here to read the full story

Grenfell Tower Inquiry: the recommendations

A full list of Sir Martin’s 17 recommendations, including calls for building owners to install facilities to give evacuation signals to tenants and cladding removal work to be completed “as vigorously as possible”.

Click here to read the full story

Grenfell Inquiry: ACM cladding was ‘primary cause of fire spread’ and tower did not comply with regulations, judge rules

The judge leading the Grenfell Tower Inquiry has ruled that the cladding installed on the tower did not comply with building regulations, finding that the polyethylene-cored panels were the “primary cause” of the rapid spread of flames.

Click here to read the full story

Grenfell Inquiry: round-up of Sir Martin Moore-Bick’s phase one conclusions

How the fire started, why the fire spread, what was the response from the fire brigade, emergency services and Kensington and Chelsea Tenant Management Organisation, all covered in our round-up of the Sir Martin’s conclusions.

Click here to read the full story

Grenfell Inquiry report: stay put ‘an article of faith’ within LFB

The inquiry judge criticises the London Fire Brigade’s “reluctance to believe that a building wouldn’t comply with building regulations” and claims that many lives would have been saved if the incident commander told residents to evacuate earlier.

Click here to read the full story

KCTMO chief criticised for ‘passive role’ and ‘ineffective leadership’ on night of Grenfell fire

Former chief executive of the Kensington and Chelsea Tenant Management Organisation was labelled as “essentially detached” from events on the night of the fire by Sir Martin. The company was also criticised for not passing on crucial resident information to the fire brigade.

Click here to read the full story

Grenfell Inquiry: ACM cladding was ‘primary cause of fire spread’ and tower did not comply with regulations

Despite saying that he would try not to deal with the make-up of the building in his phase one report, Sir Martin decided to make an early finding that the building breached headline regulation. He also ruled that the building suffered “total failure of compartmentation”.

Click here to read the full story

Grenfell Inquiry reaction: survivors call for implementation timeline for recommendations

Survivors group Grenfell United calls for fire service bosses to “face consequences” for failings leading up to the fire, while the London Fire Brigade, National Housing Federation and Royal Borough of Kensington and Chelsea also respond

Click here to read the full story

Recommendation rejected by Pickles as ‘disproportionate’ in 2013 repeated in Grenfell Tower Inquiry

Story reveals that as communities secretary Eric Pickles was given a recommendation after the Lakanal House Fire to ensure all high-rises “provide relevant information on or near premises” but branded a move to implement “unnecessary and disproportionate”

Click here to read the full story

Grenfell judge calls for Johnson to implement Grenfell Inquiry recommendations ‘without delay’

Grenfell judge calls for Johnson to implement Grenfell Inquiry recommendations ‘without delay’ In a letter to prime minister Boris Johnson before the inquiry was published, report author, Sir Martin Moore-Bick, calls on PM to implement inquiry recommendations “without delay”.

Click here to read the full story

Government to implement Grenfell Inquiry recommendations ‘in full’ and provide funding

Robert Jenrick, housing secretary, promises to bring in all of Sir Martin’s recommendations “without delay” and also guarantees government will pay for changes.

Click here to read the full story

Government to implement Grenfell Inquiry recommendations in full

Ministers will implement recommendations put forward in the Grenfell Tower Inquiry’s first report “in full” and “without delay”, housing secretary Robert Jenrick has confirmed.

Click here to read the full story

Stay Put: where did it come from and where do we go next?

“Stay put had become an article of faith and to depart from it was unthinkable.” These are the words of Grenfell Inquiry judge Sir Martin Moore-Bick. Peter Apps looks at where the idea came from and where we go now.

Click here to read the full story

Is your approach to fire safety reliant on faith in the system or good judgement?

The Grenfell Tower Inquiry report suggests that housing providers and the fire service have not been willing enough to plan for worst-case scenario fires in high-rise buildings. Martin Hilditch outlines how the inquiry’s report should guide thinking and practice

Click here to read the full story

Linked InTwitterFacebookeCard
Add New Comment
You must be logged in to comment.